Appendix E. FABRICATION AND MAINTENANCE PRACTICES
Design and construct equipment to protect personnel. First-line
and backup safeguards should be provided to prevent personnel from accessing
energized circuits. Establish
periodic tests to verify that these protective systems are operative.
E1. Equipment Acceptability
Electrical equipment is considered
safe only when it is used as specifically intended by its listing and design.
Equipment must not be altered beyond the original design intent, and must not
be used for any purpose other than that for which it was constructed.
Any equipment that is being recommissioned
must be examined and/or tested, as appropriate, to verify the status of all
safety features and the integrity of construction.
- Electrical equipment should be listed or labeled by a Nationally Recognized Testing Laboratory (NRTL).
- The division responsible for the equipment must maintain all documentation
pertaining to the design safety features of the equipment, including any test
data. This documentation must be available to any safety inspector.
- The inspector may require that equipment that is not NRTL-listed
undergo inspection and/or testing for conformance to standards. Such testing
should be documented and submitted to EH&S for approval. The inspection
record must specify, at minimum:
- Equipment identification;
- Evaluator name, date, mailstop, and extension;
- Standard to which equipment is being evaluated;
- Specific tests, results, and areas of examination;
- Any conditions of product acceptability or limitations of use.
E2. Equipment Safety Practices
- Cable Clamping: A suitable mechanical-strain-relief device such as a cord
grip, cable clamp, or plug must be used for any wire or cable penetrating
an enclosure where external movement or force can exert stress on the internal
connection. Grommets, adlets, or similar devices must not be used as
strain relief.
- Emergency Lighting: Make emergency lighting available in case normal lighting
fails when work is being conducted on energized components. (Emergency lighting
is not necessary for Class 1A and 1B work. See Hazard Class Charts in Sections
8.7.3.1 and 8.7.3.2).
- Flammable and Toxic Material Control: Keep the use of flammable or toxic
material to a minimum. A catch basin or other approved method must be provided to prevent
the spread of these materials should the normal component case fail.
- Isolation: Isolate all sources of dangerous voltage and current with covers and enclosures.
Access to lethal circuits (greater than 50V) must be either via screw-on panels
(each containing no fewer than four screws or bolts) or via interlocked doors,
panels, covers, etc. The frame or chassis of the conductive enclosure must be bonded to electrical ground with a conductor capable of
handling any potential fault current.
- Lighting: Provide adequate lighting for easy visual inspection.
- Disconnecting Means and Overload Protection: Provide overload protection and well-marked disconnects. Local “off”
controls must be provided on remote-controlled equipment.
- All disconnects and breakers must be clearly labeled to identify the loads
they control.
- Power: All ac and dc power cabling to equipment not having a separate external
ground but having line-to-line or line-to-ground voltage
greater than 50V must have an equipment-grounding conductor unless cabling
is inside an interlocked enclosure, rack, grounded
wireway, or conduit, or feeds a commercial double-insulated
or UL-listed ungrounded device.
If the grounding of equipment introduces a greater hazard, the equipment must
not be grounded.
- Rating: Operate all conductors, switches, resistors, etc., within their
design capabilities. Pulsed equipment must not exceed either
the average, the rms, or the peak rating of components. The equipment
must be derated as necessary for the environment and the application of the
components.
- Safety Grounding of Capacitive Components: Use automatic-discharge devices
on equipment with stored energy of 100J or more. Suitable and visible manual-grounding
devices must also be provided to short-to-ground all dangerous equipment while
work is being performed.
- Electrical Equipment Rooms: Place an identifying label or sign on the door
when equipment that may require servicing, manipulation, or inspection is
concealed in an equipment closet or otherwise is obscured behind doors or
panels.
- Reuse of Circuit Breakers: Do not purchase used or reconditioned circuit
breakers from vendors outside LBNL. Reuse of LBNL circuit breakers is permitted
only after the circuit breaker has been tested by the Electric Shop.
E3. Enclosures
The following specifications apply
to circuits operating at greater than 50V, or storing more than 100J. An enclosure
may be a room, a barricaded area, or an equipment cabinet:
- Access: Interlock easily opened doors, hinged panels, etc., that allow ready
access to exposed energized
components so that the act of opening de-energizes the circuit. Automatic
discharge of stored-energy devices must be provided.
See Appendix I, Large Capacitor Hazards, in this chapter.
- Doors: Doors should be key-locked, and the same key should also be used
for the locks in the control-circuit interlock chain, if applicable. This
key must not be able to be removed from the door unless the door is closed
and locked.
- Heat: Mount heat-generating components, such as resistors, so that heat
is safely dissipated and does not affect adjacent components.
- Isolation: Ensure that the enclosure physically prevents contact with live
circuits. The enclosure can be constructed of conductive or nonconductive material.
If conductive, the material
must be electrically bonded and connected to a good electrical ground. These
connections must be adequate to carry all potential fault currents.
- Seismic Safety: Secure all racks, cabinets, chassis, and auxiliary equipment
against movement during earthquakes. (See PUB 3000, Chapter 23, Seismic
Safety.)
- Strength: Ensure that enclosures are strong enough to contain flying debris
caused by component failure.
- Ventilation: Ensure that ventilation is adequate to prevent overheated equipment,
and to purge toxic fumes produced by an equipment fault. Ventilation openings
must not be obstructed.
- Visibility: Ensure that enclosures large enough to be occupied by personnel
allow exterior observation of equipment and personnel working inside the enclosure.
- Warning Indicators: When systems other than conventional facilities represent
Class 4A, 4B, or 3B hazards (see Hazard Class Charts in Sections 8.7.3.1
and 8.7.3.2), provide those systems with at least one of
these safety measures:
- A
conspicuous visual indicator that is clearly visible from any point where
a person might make hazardous contact or entry.
- A
clearly visible primary circuit breaker or “off” control button on the front
of the enclosure.
- Be
aware, however, that industrial systems may vary from these standards.